Search
Generic filters

Freezer Floor Frost Heave Prevention

Subfreezing temperatures inside cold rooms, freezers, and ice arenas cause heat to be lost from the soil under the floor, even when it is well insulated. As the soil freezes, capillary action draws water into the frozen areas where the water forms a concentrated ice mass, known as an Ice Lens. As the Ice Lens grows, it heaves the freezer floor and columns, causing damage. Chromalox frost heave protection systems are designed to prevent an Ice Lens by keeping the soil underneath warm. The Chromalox frost heave prevention system is comprised of the following:

Use of Heat Trace in the Application:

CPR SELF REGULATING CABLE – Chromalox’s CPR Cable is designed to keep soil underneath cold rooms from freezing. Our CPR cable is constructed of a self-regulating polymer core that automatically & efficiently adjusts its heat output to changes in soil temperature along the length of the conduit. Chromalox’s CPR cable can be cut-to length to easily be pulled through conduit to protect soil from freezing temperatures. Chromalox’s CPR Heating Cable is available in four watt densities – 3, 5, 8 & 10 watts/ft and is approved for installation inside of conduit. Chromalox’s CPR Heating Cable is available for 120V or 208-277V and features 16 gauge copper bus wires to permit maximize circuit lengths. Our CPR Heating Cable is available with either a modified polyolefin or fluoropolymer jacket to protect the cables from abrasion and abuse.

CZH CONSTANT WATTAGE CABLE – Chromalox CZH constant-wattage heating cable is a proven, reliable solution for frost heave prevention. CZH cable features a parallel heating core that produces uniform thermal output – over its entire length. It is flexible at most ambient temperatures and can be easily pulled through conduit. It is rugged, easy to monitor and maintain temperature, and has zero inrush at start-up. With a fIuoropolymer electrical insulation over jacketing, CZH cable has out-standing electrical and thermal properties, and is well suited for frost heave prevention. An extensive range of wattages and voltages is available immediately from Chromalox stock.

CMI HDPE JACKETED COPPER MI CABLE – Chromalox CMI cables are copper-sheathed, mineral insulated heating cables that are covered with an extruded high-density polyethylene (HDPE) jacket and are supplied as complete factory-assembled cables ready to connect to a junction box. The series-type technology, inherent to all mineral insulated heating cables, provides a reliable and consistent heat source that is ideal for frost heave prevention

Important Design Notes/Best Practices:

FOR SELF-REGULATING AND CONSTANT WATTAGE CABLES:

After determining the approximate total length of heating cable, the number of circuits, and the junction box location, do a trial layout. In making the trial layout, follow these recommendations:

FOR MINERAL INSULATED CABLES:

Let us put our experience and expertise to work for you